Ravimax Coupler's Technical Specifications
Standards Recommending Couplers
ACI 318-2008 CLAUSE 12.14.3.2
A full mechanical connection shall develop in tension or compression, as required, at least 125% of specified yield strength of the steel bar
BS 8110 : 1997 CLAUSE 3.12.8.16.
The only form of full strength mechanical joint for a bar in tension comprises a mechanical coupler satisfying the following criteria.
IS 16172 :2014 ICS 77.140.15
The Indian standard for Reinforcement Couplers for mechanical splices of bars in concrete
Ravimax Rolltech Couplers Specifications
Rebar Dia | 16 mm | 20 mm | 25 mm | 28 mm | 32 mm | 40 mm |
Grade of Rebar | Fe 500 | Fe 500 | Fe 500 | Fe 500 | Fe 500 | Fe 500 |
Internal Threading | Parallel | Parallel | Parallel | Parallel | Parallel | Parallel |
Outer Diameter (Tolerance = +/ -1mm) | 25 mm | 32 mm | 40 mm | 44 mm | 50 mm | 63 mm |
Type of failure upon ultimate Tensile Load | Strength equivalent to parent rebar | |||||
Length of Coupler (Tolerance = + 05% | 40 mm | 50 mm | 60 mm | 69 mm | 72 mm | 100 mm |
No of threads on rebar (Nos) | 08 – 09 | 10 – 11 | 10 – 11 | 11 – 12 | 11 – 12 | 13 – 14 |
Threading Req. on rebar End mm (+/-5%mm) | 20 – 22.5 | 25 – 27.5 | 30 – 33 | 33 – 36 | 33 – 36 | 49 – 52.5 |
Parallel Thread Size (Pitch) | 2.50mm | 2.50mm | 3.00mm | 3.00mm | 3.00mm | 3.50mm |
Coupler Type as per ACI 318-2008 | Type 1 | Type 1 | Type 1 | Type 1 | Type 1 | Type 1 |